Honeywell XNX-AMAV-NNIC1 XNX Gas Detector HART over 4-20mA output MPD IR CO2 sensor

description:XNX Gas Detector, HART® over 4-20mA output, ATEX/IECEx/INMETRO, 4 x M25 entries, painted Aluminium, includes MPD IR CO2 sensor 0-5%v/v...
BASIC INFO

Honeywell XNX-AMAV-NNIC1 XNX Gas Detector HART over 4-20mA output MPD IR CO2 sensor 0-5%v/v

 

XNX Gas Detector, HART® over 4-20mA output, ATEX/IECEx/INMETRO, 4 x M25 entries, painted Aluminium, includes MPD IR CO2 sensor 0-5%v/v

 

 

Product Overview


XNX's advantage comes from a simple-to-use, low-maintenance universal platform that works with other safety equipment on a digital bus system, including Honeywell Analytics’ own Searchline Excel, Optima or other gas detectors, industry standard PLCs and third-party gas monitoring controllers.

 

XNX supports Electrochemical, Infrared and Catalytic Bead gas monitors and uses standard 4-20mA wiring and HART; options include Modbus, Fieldbus (pending) up to three relays and a local Hart Adapter for configuration and diagnostics using existing HART handheld devices.

 

With 200+ unique configurations, XNX satisfies Class 1/Class 2 intrinsically safe, explosion-proof requirements in upstream/downstream oil, chemical, wastewater and other industries.

 

The enclosure is available in stainless steel or aluminum, with a marine-grade coating. Five threaded ports, available in metric or NPT versions, and ruggedized mounting options provide ultimate installation flexibility. Instrumentation built on various sensing technologies can be attached locally to the transmitter or remotely with the appropriate accessories.

 

 
Supports the widest range of sensors on a common platform and offers a modular choice of inputs and outputs (saving customers time and money).
Features & Benefits
  • Flammable gas detection 0 to 100% LFL/LEL
  • Flexible operation options
  • Minimal training required

High performance


• Flammable gas detection 0 to 100% LFL/LEL
• Point IR with heated optics provides immunity to poisoning and no hidden faults
• Open-path IR flammable gas detection inLEL-m measurement
• Electrochemical cell offers toxic gas detection in ppm
• IR cell provides CO2 and combustible gas monitoring
• Robust and reliable operation in explosive areas and harsh environments

 

Flexible Operation
• 3 versions - supports (Catalytic Bead and IR Cell),Electrochemical Cell and IR (point and open-path)
gas detection
• Multi-Purpose Detector (MPD) with field serviceable mV,Catalytic bead and IR Cell capability
• 4-20mA with HART as standard
• HART Enhanced Device Description Language(EDDL) software*
• Multiple communications options include up to 3 relays,MODBUS and FOUNDATION H1 Fieldbus
• Optional local IS port for handheld HART configurator
 
Easy to Use
• Large, backlit, easy-to-view LCD display offers multisensory indicators (visual icons, colored buttons, text,
etc.) to display gas and sensor readings
• User interface supported by 8 selectable languages (English, Spanish, German, Italian, Portuguese, French,
Russian, Chinese)
• Self-test and fault indication features
• Non-intrusive, one-man operation
• Quick calibration with auto-inhibit
 
 
Easy to Install
• 3 or 4 wire operation, source, sink or isolated
• Simple plug-in sensors and replaceable cells
• NEMA 4X IP66 rated for rugged indoor/outdoor use
• Five conduit entries for ease of installation
 
Cost Effective
• Minimal training required
• One-man operation
• Plug-in sensor replacement
• All necessary accessories included
Quick Specs
  • Material: LM25 aluminum, painted (SS316 painted optional)
  • Temperature: -40° to +65°C / -40° to +150°F (sensor dependent)
  • Humidity: 20 to 90% RH (non-condensing) 

 

 

 Model selections:

XNX Universal Transmitter- Flammable Standard Temperature with MPD sensor
XNX Universal transmitter for the Multi - Purpose Detector (MPD) sensor for flammable gases.

 

XNX Aluminium Transmitter ATEX/IEC/INMETRO with MPD Flammable Catalytic Sensor 0-100%LEL

 

XNX-AMAV-NNCB1 XNX Gas Detector, HART® over 4-20mA output, ATEX/IECEx/INMETRO, 4 x M25
entries, painted Aluminium, includes MPD catalytic sensor 0-100%LEL

XNX-AMAV-NHCB1 XNX Gas Detector, HART® over 4-20mA output and local HART® interface port,
ATEX/IECEx/INMETRO, 3 x M25 entries, painted Aluminium, includes MPD catalytic sensor 0-100%LEL

XNX-AMAV-RNCB1 XNX Gas Detector, HART® over 4-20mA output and 3 fault/alarm relays,
ATEX/IECEx/INMETRO, 4 x M25 entries, painted Aluminium, includes MPD catalytic sensor 0-100%LEL

XNX-AMAV-RHCB1 XNX Gas Detector, HART® over 4-20mA output, 3 fault/alarm relays and local HART®
interface port, ATEX/IECEx/INMETRO, 3 x M25 entries, painted Aluminium, includes MPD catalytic sensor 0-100%LEL

XNX-AMAV-MNCB1 XNX Gas Detector, HART® over 4-20mA and Modbus output, ATEX/IECEx/INMETRO, 4
x M25 entries, painted Aluminium, includes MPD catalytic sensor 0-100%LEL

XNX-AMAV-MHCB1 XNX Gas Detector, HART® over 4-20mA and Modbus output and local HART® interface
port, ATEX/IECEx/INMETRO, 3 x M25 entries, painted Aluminium, includes MPD catalytic sensor 0-100%LEL

XNX-AMAV-FNCB1 XNX Gas Detector, HART® over 4-20mA and Foundation Fieldbus™ output,
ATEX/IECEx/INMETRO, 4 x M25 entries, painted Aluminium, includes MPD catalytic sensor 0-100%LEL

XNX-AMAV-FHCB1 XNX Gas Detector, HART® over 4-20mA and Foundation Fieldbus™ output and local
HART® interface port, ATEX/IECEx/INMETRO, 3 x M25 entries, painted Aluminium,
includes MPD catalytic sensor 0-100%LEL

 

 

XNX Stainless Steel Transmitter ATEX/IEC with MPD Flammable Catalytic Sensor 0-100%LEL

 

XNX-AMSV-NNCB1 XNX transmitter, HART?over 4-20mA output, ATEX/IEC approved, 5 x M25 entries,
painted 316 stainless steel, including MPD catalytic sensor 0-100%LEL.

XNX-AMSV-NHCB1 XNX transmitter, HART?over 4-20mA output, ATEX/IEC approved, 5 x M25 entries,
painted 316 stainless steel, with local HART?interface port, including MPD catalytic sensor 0-100%LEL.

XNX-AMSV-RNCB1 XNX transmitter, HART?over 4-20mA output, ATEX/IEC approved, 5 x M25 entries,
painted 316 stainless steel, with alarm and fault relay outputs, including MPD catalytic
sensor 0-100%LEL.

XNX-AMSV-RHCB1 XNX transmitter, HART?over 4-20mA output, ATEX/IEC approved, 5 x M25 entries,
painted 316 stainless steel, with alarm and fault relay outputs and local HART interface port, including MPD catalytic sensor 0-100%LEL

XNX-AMSV-MNCB1 XNX transmitter, HART® over 4-20mA output, ATEX/IEC approved, 5 x M25 entries,
painted 316 stainless steel, with Modbus® output, including MPD catalytic sensor 0- 100%LEL.

XNX-AMSV-MHCB1 XNX transmitter, HART® over 4-20mA output, ATEX/IEC approved, 5 x M25 entries,
painted 316 stainless steel, with Modbus® output and local HART® interface port including MPD catalytic sensor 0-100%LEL.

XNX-AMSV-FNCB1 XNX transmitter, HART® over 4-20mA output, ATEX/IEC approved, 5 x M25 entries,
painted 316 stainless steel, with optional Foundation Fieldbus™ output, including MPD
catalytic sensor 0-100%LEL.

XNX-AMSV-FHCB1 XNX transmitter, HART® over 4-20mA output, ATEX/IEC approved, 5 x M25 entries,
painted 316 stainless steel, with optional Foundation Fieldbus™ output and local HART®
interface port, including MPD catalytic sensor 0-100%LEL.

 

 

XNX Aluminium Transmitter ATEX/IEC/INMETRO with MPD IR Hydrocarbon (Propane) Sensor 0-100%LEL

 

XNX-AMAV-NNIF1 XNX Gas Detector, HART?over 4-20mA output, ATEX/IECEx/INMETRO, 4 x M25
entries, painted Aluminium, includes MPD IR hydrocarbon (Propane) sensor 0-100%LEL

XNX-AMAV-NHIF1 XNX Gas Detector, HART?over 4-20mA output and local HART?interface port,
ATEX/IECEx/INMETRO, 3 x M25 entries, painted Aluminium, includes MPD IR hydrocarbon (Propane) sensor 0-100%LEL

XNX-AMAV-RNIF1 XNX Gas Detector, HART?over 4-20mA output and 3 fault/alarm relays,
ATEX/IECEx/INMETRO, 4 x M25 entries, painted Aluminium, includes MPD IR hydrocarbon (Propane) sensor 0-100%LEL

XNX-AMAV-RHIF1 XNX Gas Detector, HART?over 4-20mA output, 3 fault/alarm relays and local HART?
interface port, ATEX/IECEx/INMETRO, 3 x M25 entries, painted Aluminium, includes MPD IR hydrocarbon (Propane) sensor 0-100%LEL

XNX-AMAV-MNIF1 XNX Gas Detector, HART?over 4-20mA and Modbus output, ATEX/IECEx/INMETRO, 4
x M25 entries, painted Aluminium, includes MPD IR hydrocarbon (Propane) sensor 0- 100%LEL

XNX-AMAV-MHIF1 XNX Gas Detector, HART?over 4-20mA and Modbus output and local HART?interface
port, ATEX/IECEx/INMETRO, 3 x M25 entries, painted Aluminium, includes MPD IR hydrocarbon (Propane) sensor 0-100%LEL

XNX-AMAV-FNIF1 XNX Gas Detector, HART?over 4-20mA and Foundation Fieldbus?output,
ATEX/IECEx/INMETRO, 4 x M25 entries, painted Aluminium, includes MPD IR hydrocarbon (Propane) sensor 0-100%LEL

XNX-AMAV-FHIF1 XNX Gas Detector, HART?over 4-20mA and Foundation Fieldbus?output and local
HART?interface port, ATEX/IECEx/INMETRO, 3 x M25 entries, painted Aluminium, includes MPD IR hydrocarbon (Propane) sensor 0-100%LEL 

 

XNX Stainless Steel Transmitter ATEX/IEC with MPD IR Hydrocarbon (Propane) Sensor 0-100%LEL

 

XNX-AMSV-NNIF1 XNX transmitter, HART® over 4-20mA output, ATEX/IEC approved, 5 x M25 entries,
painted 316 stainless steel, including MPD IR flammable (propane) sensor 0- 100%LEL.

XNX-AMSV-NHIF1 XNX transmitter, HART® over 4-20mA output, ATEX/IEC approved, 5 x M25 entries,
painted 316 stainless steel, with local HART® interface port, including MPD IR flammable sensor 0-100%LEL.

XNX-AMSV-RNIF1 XNX transmitter, HART® over 4-20mA output, ATEX/IEC approved, 5 x M25 entries,
painted 316 stainless steel, with alarm and fault relay outputs, including MPD IR flammable sensor 0-100%LEL.

XNX-AMSV-RHIF1 XNX transmitter, HART® over 4-20mA output, ATEX/IEC approved, 5 x M25 entries,
painted 316 stainless steel, with alarm and fault relay outputs and local HART® interface
port, including MPD IR flammable sensor 0-100%LEL.

XNX-AMSV-MNIF1 XNX transmitter, HART® over 4-20mA output, ATEX/IEC approved, 5 x M25 entries,
painted 316 stainless steel, with Modbus® output, including MPD IR flammable sensor 0-100%LEL.

XNX-AMSV-MHIF1 XNX transmitter, HART® over 4-20mA output, ATEX/IEC approved, 5 x M25 entries,
painted 316 stainless steel, with Modbus® output and local HART® interface port, including MPD IR flammable sensor 0-100%LEL.

XNX-AMSV-FHIF1 XNX transmitter, HART?over 4-20mA output, ATEX/IEC approved, 5 x M25 entries,
painted 316 stainless steel, with optional Foundation Fieldbus?output and local HART interface port, including MPD IR flammable sensor 0-100%LEL.

XNX-AMSV-FNIF1 XNX transmitter, HART® over 4-20mA output, ATEX/IEC approved, 5 x M25 entries,
painted 316 stainless steel, with optional Foundation Fieldbus™ output, including MPD IR flammable sensor 0-100%LEL.

 

XNX Aluminium Transmitter ATEX/IEC/INMETRO with MPD Infrared Methane Sensor 0-100%LEL (0-5%V/V).

 

XNX-AMAV-NNIV1 XNX Gas Detector, HART® over 4-20mA output, ATEX/IECEx/INMETRO, 4 x M25
entries, painted Aluminium, includes MPD IR hydrocarbon (Methane) sensor 0-100%LEL (0-5%v/v)

XNX-AMAV-NHIV1 XNX Gas Detector, HART® over 4-20mA output and local HART® interface port,
ATEX/IECEx/INMETRO, 3 x M25 entries, painted Aluminium, includes MPD IR hydrocarbon (Methane) sensor 0-100%LEL (0-5%v/v)

XNX-AMAV-RNIV1 XNX Gas Detector, HART® over 4-20mA output and 3 fault/alarm relays,
ATEX/IECEx/INMETRO, 4 x M25 entries, painted Aluminium, includes MPD IR hydrocarbon (Methane) sensor 0-100%LEL (0-5%v/v)

XNX-AMAV-RHIV1 XNX Gas Detector, HART® over 4-20mA output, 3 fault/alarm relays and local HART®
interface port, ATEX/IECEx/INMETRO, 3 x M25 entries, painted Aluminium, includes
MPD IR hydrocarbon (Methane) sensor 0-100%LEL (0-5%v/v)

XNX-AMAV-MNIV1 XNX Gas Detector, HART® over 4-20mA and Modbus output, ATEX/IECEx/INMETRO, 4
x M25 entries, painted Aluminium, includes MPD IR hydrocarbon (Methane) sensor 0- 100%LEL (0-5%v/v)

XNX-AMAV-MHIV1 XNX Gas Detector, HART® over 4-20mA and Modbus output and local HART® interface
port, ATEX/IECEx/INMETRO, 3 x M25 entries, painted Aluminium, includes MPD IR
hydrocarbon (Methane) sensor 0-100%LEL (0-5%v/v)

XNX-AMAV-FNIV1 XNX Gas Detector, HART® over 4-20mA and Foundation Fieldbus™ output,
ATEX/IECEx/INMETRO, 4 x M25 entries, painted Aluminium, includes MPD IR hydrocarbon (Methane) sensor 0-100%LEL (0-5%v/v)


XNX-AMAV-FHIV1 XNX Gas Detector, HART® over 4-20mA and Foundation Fieldbus™ output and local
HART® interface port, ATEX/IECEx/INMETRO, 3 x M25 entries, painted Aluminium, includes MPD IR hydrocarbon (Methane) sensor 0-100%LEL (0-5%v/v)


XNX Stainless Steel Transmitter ATEX/IEC with MPD Infrared Methane Sensor 0-100%LEL (0-5%V/V).

 

XNX-AMSV-NNIV1 XNX transmitter, HART® over 4-20mA output, ATEX/IEC approved, 5 x M25 entries,
painted 316 stainless steel, including MPD IR methane sensor 0-100%LEL (0-5%V/V).

XNX-AMSV-NHIV1 XNX transmitter, HART® over 4-20mA output, ATEX/IEC approved, 5 x M25 entries,
painted 316 stainless steel, with optional local HART® interface port, including MPD IR methane sensor 0-100%LEL (0-5%V/V).

XNX-AMSV-RNIV1 XNX transmitter, HART® over 4-20mA output, ATEX/IEC approved, 5 x M25 entries,
painted 316 stainless steel, with optional alarm and fault relay outputs, including MPD IR methane sensor 0-100%LEL (0-5%V/V).

XNX-AMSV-RHIV1 XNX transmitter, HART® over 4-20mA output, ATEX/IEC approved, 5 x M25 entries,
painted 316 stainless steel, with optional alarm and fault relay outputs and local HART ® interface port, including MPD IR methane sensor 0-100%LEL (0-5%V/V).

XNX-AMSV-MNIV1 XNX transmitter, HART® over 4-20mA output, ATEX/IEC approved, 5 x M25 entries,
painted 316 stainless steel, with optional Modbus® output, including MPD IR methane sensor 0-100%LEL (0-5%V/V).

XNX-AMSV-MHIV1 XNX transmitter, HART® over 4-20mA output, ATEX/IEC approved, 5 x M25 entries,
painted 316 stainless steel, with optional Modbus® output and local HART® interface port, including MPD IR methane sensor 0-100%LEL (0-5%V/V).

XNX-AMSV-FNIV1 XNX transmitter, HART® over 4-20mA output, ATEX/IEC approved, 5 x M25 entries,
painted 316 stainless steel, with optional Foundation Fieldbus™ output, including MPD IR methane sensor 0-5%V/V.

XNX-AMSV-FHIV1 XNX transmitter, HART® over 4-20mA output, ATEX/IEC approved, 5 x M25 entries,
painted 316 stainless steel, with optional Foundation Fieldbus™ output and local HART® interface port, including MPD IR methane sensor 0-5%V/V.

 

XNX Aluminium Transmitter ATEX/IEC/INMETRO with MPD Infrared CO2 Sensor 0-5%V/V.

 

XNX-AMAV-NNIC1 XNX Gas Detector, HART® over 4-20mA output, ATEX/IECEx/INMETRO, 4 x M25
entries, painted Aluminium, includes MPD IR CO2 sensor 0-5%v/v

XNX-AMAV-NHIC1 XNX Gas Detector, HART® over 4-20mA output and local HART® interface port,
ATEX/IECEx/INMETRO, 3 x M25 entries, painted Aluminium, includes MPD IR CO2 sensor 0-5%v/v

XNX-AMAV-RNIC1 XNX Gas Detector, HART® over 4-20mA output and 3 fault/alarm relays,
ATEX/IECEx/INMETRO, 4 x M25 entries, painted Aluminium, includes MPD IR CO2 sensor 0-5%v/v

XNX-AMAV-RHIC1 XNX Gas Detector, HART® over 4-20mA output, 3 fault/alarm relays and local HART®
interface port, ATEX/IECEx/INMETRO, 3 x M25 entries, painted Aluminium, includes MPD IR CO2 sensor 0-5%v/v

XNX-AMAV-MNIC1 XNX Gas Detector, HART® over 4-20mA and Modbus output, ATEX/IECEx/INMETRO, 4
x M25 entries, painted Aluminium, includes MPD IR CO2 sensor 0-5%v/v

XNX-AMAV-MHIC1 XNX Gas Detector, HART® over 4-20mA and Modbus output and local HART® interface
port, ATEX/IECEx/INMETRO, 3 x M25 entries, painted Aluminium, includes MPD IR CO2 sensor 0-5%v/v

XNX-AMAV-FNIC1 XNX Gas Detector, HART® over 4-20mA and Foundation Fieldbus™ output,
ATEX/IECEx/INMETRO, 4 x M25 entries, painted Aluminium, includes MPD IR CO2 sensor 0-5%v/v

XNX-AMAV-FHIC1 XNX Gas Detector, HART® over 4-20mA and Foundation Fieldbus™ output and local
HART® interface port, ATEX/IECEx/INMETRO, 3 x M25 entries, painted Aluminium, includes MPD IR CO2 sensor 0-5%v/v

 

XNX Stainless Steel Transmitter ATEX/IEC with MPD Infrared CO2 Sensor 0-5%V/V.

 

XNX-AMSV-NNIC1 XNX transmitter, HART® over 4-20mA output, ATEX/IEC approved, 5 x M25 entries,
painted 316 stainless steel, including MPD IR CO2 sensor 0-5%V/V.

XNX-AMSV-NHIC1 XNX transmitter, HART® over 4-20mA output, ATEX/IEC approved, 5 x M25 entries,
painted 316 stainless steel, with local HART® interface port, including MPD IR CO2 sensor 0-5%V/V.

XNX-AMSV-RNIC1 XNX transmitter, HART® over 4-20mA output, ATEX/IEC approved, 5 x M25 entries,
painted 316 stainless steel, with alarm and fault relay outputs, including MPD IR CO2 sensor 0-5%V/V.

XNX-AMSV-RHIC1 XNX transmitter, HART® over 4-20mA output, ATEX/IEC approved, 5 x M25 entries,
painted 316 stainless steel, with alarm and fault relay outputs and local HART® interface
port, including MPD IR CO2 sensor 0-5%V/V.

XNX-AMSV-MNIC1 XNX transmitter, HART® over 4-20mA output, ATEX/IEC approved, 5 x M25 entries,
painted 316 stainless steel, with Modbus® output, including MPD IR CO2 sensor 0- 5%V/V.

XNX-AMSV-MHIC1 XNX transmitter, HART® over 4-20mA output, ATEX/IEC approved, 5 x M25 entries,
painted 316 stainless steel, with Modbus® output and local HART® interface port,
including MPD IR CO2 sensor 0-5%V/V.

XNX-AMSV-FNIC1 XNX transmitter, HART® over 4-20mA output, ATEX/IEC approved, 5 x M25 entries,
painted 316 stainless steel, with optional Foundation Fieldbus™ output, including MPD
IR CO2 sensor 0-5%V/V.

XNX-AMSV-FHIC1 XNX transmitter, HART® over 4-20mA output, ATEX/IEC approved, 5 x M25 entries,
painted 316 stainless steel, with optional Foundation Fieldbus™ output and local HART®
interface port, including MPD IR CO2 sensor 0-5%V/V.

 


-----------------------------------